TM 9-2320-365-10
Table 3-2. Troubleshooting (Cont)
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
e107.
M1079 110 VAC OUTLET J231 DOES NOT OPERATE (CONT).
(b)
If circuit breaker is tripped, position to ON to reset.
(c)
Check to see if 110 vac outlet J231 operates.
(d)
If 110 vac outlet J231 does not operate, or circuit breaker trips again, notify Unit
Maintenance.
e108.
M1079 110 VAC OUTLET J230 DOES NOT OPERATE.
Check circuit breaker (CB9) in 110/208 VAC POWER DISTRIBUTION PANEL to see if it is tripped.
(a)
Open 110/208 VAC POWER DISTRIBUTION PANEL cover (para 2-32).
(b)
If circuit breaker is tripped, position to ON to reset.
(c)
Check to see if 110 vac outlet J230 operates.
(d)
If 110 vac outlet J230 does not operate, or circuit breaker trips again, notify Unit
Maintenance.
e109.
M1079 BLACKOUT LIGHT(S) DOES NOT ILLUMINATE.
Check circuit breaker (CB11) on relay box to see if it is tripped.
(a)
If circuit breaker is tripped, push in to reset.
(b)
Check to see if blackout lights operate.
(c)
If blackout lights do not illuminate, or circuit breaker trips again, notify Unit Maintenance.
e110.
ONE OR MORE M1079 EMERGENCY LIGHTS DO NOT ILLUMINATE.
Check circuit breaker (CB11) on relay box to see if it is tripped.
(a)
If circuit breaker is tripped, push in to reset.
(b)
Check to see if emergency lights operate.
(c)
If emergency lights do not illuminate, or circuit breaker trips again, notify Unit Maintenance.
e111.
M0179 FIELD PHONE 1 AND/OR 2 BINDING POST DOES NOT OPERATE.
Notify Unit Maintenance.
e112.
M1079 AIR CONDITIONER DOES NOT OPERATE.
Check circuit breaker (CB2) in 110/208 VAC POWER DISTRIBUTION PANEL to see if it is tripped.
(a)
Open 110/208 VAC POWER DISTRIBUTION PANEL cover (para 2-32).
Change 1
3-67